Fusetron™ FRN-R Class RK5 250Vac/125Vdc 1⁄10-60A, dual element, time-delay fuses
-
Fusetron™ FRN-R Class RK5 250Vac, 125/250Vdc 70-600A, dual element, time-delay fuses
Fusetron™ FRN-R Class RK5 250Vac/125Vdc 1⁄10-60A, dual element, time-delay fuses
Catalog symbols:
-
FRN-R-_ (non-indicating)
-
FRN-R-_ID (indicating)
Description:
Eaton Bussmann® series advanced protection, energy efficient FRN-R Class RK5 dual element, current-limiting, time-delay fuses with optional open fuse indication on select ratings. Time-delay – 10 seconds (minimum) at 500% of rated current (8 seconds for 1⁄10-30A sizes).
Specifications:
Ratings :
Volts :
-
250Vac
-
125Vdc
Amps : 1⁄10-60A
Interrupting rating :
-
200kA Vac RMS Sym.
-
20kA Vdc
Agency information
-
UL Listed, Std. 248-12, Class RK-5, Guide JDDZ, File E4273
-
CSA Certified, C22.2 No. 248.12, Class 1422- 02, File 53787
-
CE
Catalog numbers (amps) — non-indictaing fuses
Catalog Numbers
Catalog Numbers
Catalog Numbers
Catalog Numbers
FRN-R-1/10
FRN-R-1-1/4
FRN-R-4
FRN-R-15
FRN-R-1/8
FRN-R-1-4/10
FRN-R-4-1/2
FRN-R-17-1/2
FRN-R-15/100
FRN-R-1-1/2
FRN-R-5
FRN-R-20
FRN-R-2/10
FRN-R-1-6/10
FRN-R-5-6/10
FRN-R-25
FRN-R-1/4
FRN-R-1-8/10
FRN-R-6
FRN-R-30
FRN-R-3/10
FRN-R-2
FRN-R-6-1/4
FRN-R-35
FRN-R-4/10
FRN-R-2-1/4
FRN-R-7
FRN-R-40
FRN-R-1/2
FRN-R-2-1/2
FRN-R-7-1/2
FRN-R-45
FRN-R-6/10
FRN-R-2-8/10
FRN-R-8
FRN-R-50
FRN-R-8/10
FRN-R-3
FRN-R-9
FRN-R-60
FRN-R-1
FRN-R-3-2/10
FRN-R-10
FRN-R-1-1/8
FRN-R-3-1/2
FRN-R-12
* Open fuse indication available by inserting the sufix “ID.” E.g., FRN-R-15ID.
Carton Quantity:
Amp Rating
Carton Qty.
1⁄10 – 60
10
Features:
-
Provides motor overload, ground fault and short-circuit protection
-
Helps protect motors against burnout from overloads
-
Helps protect motors against burnout from single-phasing on three-phase systems
-
Simplifies and improves blackout prevention (selective coordination)
-
Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short-circuit and overload protection
-
The overload element provides protection against low level overcurrent of overloads and will hold an overload which is five times greater than the ampere rating of the fuse for a minimum of ten seconds
Recommended fuse blocks:
Fuse amps
1-Pole
2-Pole
3-Pole
up to 30
RM25030-1_
RM25030-2_
RM25030-3_
35 to 60'
RM25060-1CR
RM25060-2CR
RM25060-3CR
For additional information see data sheet no. 10289.
Fuse reducers for Class R fuses
Fuse size
Amp size of fuse block or disconnect switch
Catalog no.
(pairs)
Up to 30A
60A
NO.263-R
Up to 30A
100A
NO.213-R
35 to 60A
NO.216-R
35 to 60A
200A
NO.226-R
For additional information on Class R fuse reducers, see data sheet no 1118.
Fusetron™ FRN-R Class RK5 250Vac, 125/250Vdc 70-600A, dual element, time-delay fuses
Catalog symbols: FRN-R-_
Description:
Eaton Bussmann® series advanced protection, energy efficient FRN-R Class RK5 dual element, current-limiting, time-delay fuses. Time-delay – 10 seconds (minimum) at 500% of rated current.
Specifications:
Ratings :
Volts :
-
250Vac
-
125Vdc (110-200A)
-
250Vdc (225-600A)
Amps : 70-600A
Interrupting rating
-
200kA Vac RMS Sym.
-
20kA Vdc
Agency information
-
UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
-
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
-
CE
Catalog numbers (amps) :
Catalog Numbers
Catalog Numbers
Catalog Numbers
Catalog Numbers
FRN-R-70
FRN-R-100
FRN-R-200
FRN-R-400
FRN-R-75
FRN-R-110
FRN-R-225
FRN-R-450
FRN-R-80
FRN-R-125
FRN-R-250
FRN-R-500
FRN-R-85
FRN-R-150
FRN-R-300
FRN-R-600
FRN-R-90
FRN-R-175
FRN-R-350
Carton Quantity:
Amp Rating
Carton Qty.
70-100
5
110-600
1
Features:
-
Provides motor overload, ground fault and short-circuit protection
-
Helps protect motors against burnout from overloads and single-phasing when sized properly
-
Simplifies and improves blackout prevention (selective coordination)
-
Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short-circuit and overload protection
-
The overload element provides protection against low level overcurrent of overloads and will hold on inrush current which is five times greater than the amp rating of the fuse for a minimum of ten seconds
Recommended fuse blocks:
Fuse amps
1-Pole
2-Pole
3-Pole
70-100
RM25100-1CR
RM25100-2CR
RM25100-3CR
110-200
RM25200-1CR
RM25200-2CR
RM25200-3CR
225-400
RM25400-1CR
RM25400-2CR
RM25400-3CR
450-600
RM25600-1CR
RM25600-2CR
RM25600-3CR
For additional information on the RM 250 volt fuse blocks, see product brochure no. 3192
use reducers for Class R fuses
Fuse size
Amp size of fuse block or disconnect switch
Catalog no.
(pairs)
65-100A
400A
NO.2641-R
110-200A
NO.242-R
65-100A
600A
NO.2664-R
110-200A
NO.2662-R
225-400A
NO.2664-R
* These reducers are not CSA Certified.
† Single reducer only (pair not required)
For additional information on Class R fuse reducers, see data sheet no 1118.
Current-limiting effects:
Prospective S.C.C.
Let-through current
(apparent RMS symmetrical vs. fuse rating)
—
100A
200A
400A
600A
5000
3000
5000
5000
5000
10000
4000
7000
10000
10000
15000
5000
8000
11000
15000
20000
5000
8000
12000
16000
25000
5000
9000
13000
17000
30000
6000
10000
14000
18000
35000
6000
10000
15000
19000
40000
7000
11000
15000
20000
50000
7000
11000
17000
21000
60000
8000
12000
18000
22000
70000
8000
13000
19000
23000
80000
8000
13000
19000
24000
90000
9000
14000
21000
25000
100000
9000
14000
21000
26000
150000
10000
16000
24000
29000
200000
11000
18000
26000
32000
-
-