600 V NOS Class K5 and H fuses
Description
Basic protection 600 V NOS Class K5 and H general purpose, noncurrent-limiting, one-time fuses.
Catalog symbol • NOS-(amp)
Ratings
• Volts 600 Vac
• Amps 1-600 A
• IR
• 50 kA Vac RMS Sym. (1-60 A)
• 10 kA Vac RMS Sym. (70-600 A)
Agency information
• UL Listed, Class K5 (1-60 A), Std. 248-9, Class H (70-600 A),Std. 248-6, UL Guide JDDZ, File E4273
• CSA Certified, Class 1421-01, File 53787
• CE
Catalog Numbers (Amps)
Catalog Numbers
Catalog Numbers
Catalog Numbers
Catalog Numbers
NOS-1
NOS-12
NOS-70
NOS-225
NOS-2
NOS-15
NOS-75
NOS-250
NOS-3
NOS-20
NOS-80
NOS-300
NOS-4
NOS-25
NOS-90
NOS-350
NOS-5
NOS-30
NOS-100
NOS-400
NOS-6
NOS-35
NOS-110
NOS-450
NOS-7
NOS-40
NOS-125
NOS-500
NOS-8
NOS-45
NOS-150
NOS-600
NOS-9
NOS-50
NOS-175
NOS-10
NOS-60
NOS-200
Carton Quantity and Weight - NOS ONE-TIME (600Vac)
Catalog Number
Carton Qty.
Weight**
Lbs
Kg.
NOS 1–30
10
1.45
0.657
NOS 35–60
10
2.6
1.179
NOS 70–100
5
2.8
1.27
NOS 110–200
1
1.24
0.562
NOS 225–400
1
3.03
1.374
NOS 450–600
1
4.63
2.1
Features
• Protect lighting, heating and other circuits not subject to temporary surges and where available short-circuit currents are relatively low
• NOS one-time fuses do not have any appreciable degree of timedelay and thus should not be specified in circuits where large transients or motor overloads occur. Use Bussmann series advanced protection FUSETRON FRS-R or ultimate protection Low-Peak LPS-RK dual-element, time-delay fuses.
• For general purpose circuits, size at amp rating of circuit
• For motor circuits, size at 300% to 400% according to the NEC® motor ampacity tables 430.247 to 430.250, per 430.6(A)(1)
Recommended fuse blocks
• 1-, 2- and 3-pole modular fuse blocks up to 600 amps — see data sheet no. 10487
• 1-, 2- and 3-pole modular power distribution fuse blocks up to 60 amps — see data sheet no. 10490
-